<p id="jg8hh"></p><delect id="jg8hh"><em id="jg8hh"><blockquote id="jg8hh"></blockquote></em></delect><acronym id="jg8hh"><dd id="jg8hh"></dd></acronym><button id="jg8hh"><dd id="jg8hh"><acronym id="jg8hh"></acronym></dd></button><samp id="jg8hh"><em id="jg8hh"><blockquote id="jg8hh"></blockquote></em></samp>

<p id="jg8hh"></p>

<samp id="jg8hh"><legend id="jg8hh"></legend></samp>
<samp id="jg8hh"><legend id="jg8hh"><samp id="jg8hh"></samp></legend></samp>

<samp id="jg8hh"></samp>

<p id="jg8hh"></p><acronym id="jg8hh"></acronym><p id="jg8hh"><dd id="jg8hh"><acronym id="jg8hh"></acronym></dd></p><p id="jg8hh"></p>

<p id="jg8hh"></p><delect id="jg8hh"><legend id="jg8hh"><var id="jg8hh"></var></legend></delect><button id="jg8hh"><listing id="jg8hh"><i id="jg8hh"></i></listing></button>
<delect id="jg8hh"><legend id="jg8hh"><var id="jg8hh"></var></legend></delect>

變頻器430報警故障代碼F0002的問題?

發(fā)布時間:2023-11-02
一臺5.5kw的變頻器控制一臺5.5kw的增壓泵,我們做系統(tǒng)嚴(yán)正,所以連續(xù)開了大約15天,然后出現(xiàn)了故障代碼f0002,后來把變頻器前面的斷路器斷開,并重新合上,恢復(fù)正常。這種情況是什么原因?什么是斜坡下降時間必須與負(fù)載的慣量相匹配?
答:關(guān)于故障f0002——
1、f0002是過壓故障。
2、可能引起故障的原因——
1)直流回路的電壓值超過了跳閘閾值;
2)由于供電電源電壓過高,或者電動機處于再生制動方式下引起過電壓;
3)斜坡下降過快,或者電動機由大慣量負(fù)載帶動旋轉(zhuǎn)而處于再生制動狀態(tài)下。
3、一般解決措施——
1)檢查電動機的動力電纜及電動機接地情況,看是否存在電纜破皮或接地不合適等現(xiàn)象。
2)增大變頻器的斜坡參數(shù) p1120、p1121的值。
3)是否配置了制動電阻?如果沒有配置的話,注意設(shè)置參數(shù) p1240=1;如果配置了制動電阻的話,注意設(shè)置參數(shù)p1240=0。
4、一般來說,變頻器在頻率上升時容易報欠壓故障,在頻率下降時容易報過壓故障。過壓故障容易在減速、制動過程中產(chǎn)生。如果說你的變頻器供電電源電壓偏高了,那樣的話,那變頻器也是會報f0002的。